Home / Commercial / Mitsubishi / Code 4250
Mitsubishi City Multi · Commercial VRF

Error Code 4250

Error 4250 is the inverter overcurrent family. Its detail code tells you whether this is a board repair or a failed compressor — a big cost difference.

Category

Compressor & Inverter

Urgency

Critical

Typical repair cost

Highest

Reported by

Outdoor unit

Can it wait?

No. This family includes faults that indicate a failed compressor or a ground fault, neither of which should be repeatedly restarted.

If it is left unresolved

Repeated restarts against a genuine overcurrent condition can damage the inverter, the compressor, or both. A fault that started on one component can take the other with it.

Preliminary code 4350. Mitsubishi reports many faults twice — a preliminary code when a problem is first detected, then the definite code once it is confirmed. Seeing 4350 is an early warning before the system locks out.

Detail codes

  • 101 IPM error — the intelligent power module protecting the inverter has faulted.
  • 103 DCCT overcurrent, detected in hardware. Current exceeded limits at the sensing circuit.
  • 104 Short-circuited IPM or ground fault. Often the most serious of the group.
  • 105 Overcurrent caused by a short-circuited motor — typically points at the compressor itself.
  • 106 Instantaneous overcurrent, detected in software. A sudden current spike.
  • 107 Overcurrent by effective value, detected in software. Sustained draw above limits.

If your Mitsubishi City Multi system is showing error code 4250, the inverter detected current beyond safe limits and shut down.

This is the code family we treat most cautiously, because it spans everything from a recoverable board fault to a failed compressor — the single most expensive repair on a VRF system.

Read the detail code first

Before anything else: write down the number in brackets.

4250 is not one fault. It is six, and the detail code is what distinguishes them:

DetailWhat it indicates
101IPM error — the power module protecting the inverter has faulted
103DCCT overcurrent detected in hardware at the sensing circuit
104Short-circuited IPM or ground fault
105Overcurrent from a short-circuited motor — points at the compressor
106Instantaneous overcurrent detected in software — a sudden spike
107Overcurrent by effective value — sustained draw above limits

The difference between 101 and 105 is roughly the difference between a board repair and a compressor replacement. That single number is the most valuable thing on your controller, and it is frequently lost because someone resets the fault before recording it.

What this means for your building

The inverter controls compressor speed by varying the power delivered to it. It monitors current continuously, because excessive current is how both inverters and compressors destroy themselves.

When current exceeds limits, the system stops immediately. That is not a graceful shutdown — it is a protective cut, and it happens fast because the alternative is component damage.

The preliminary code

4350 is the preliminary code for 4250. If it appears in your fault history, the system detected the condition before it became a lockout.

Preliminary codes in this family are worth taking seriously. A compressor developing a winding fault or an inverter with a degrading power module often signals before it fails outright.

How urgent is it?

Critical. This is the code where continuing to run the system is genuinely capable of turning one expensive repair into two.

If the underlying condition is a short circuit or ground fault, each restart drives fault current through components already compromised. A failed compressor can take a healthy inverter with it. An inverter with a failing power module can damage a healthy compressor.

No safety hazard to occupants, but real risk to equipment with every restart attempt.

What it typically costs

Highest. This is the top of the cost range for VRF faults.

At the lower end, an inverter board fault is a significant but bounded repair. At the upper end, a short-circuited compressor means the compressor itself, refrigerant recovery, system cleanup where contamination has occurred, and substantial labour to remove and replace a large component in a commercial setting.

There is also a scenario worth knowing about: when a compressor fails electrically, it can contaminate the refrigerant circuit. Cleaning that up properly adds materially to the job, and skipping it puts the replacement compressor at risk.

What causes it

  • Compressor winding failure or short — the expensive scenario, typically detail code 105
  • Inverter power module failure — detail codes 101 or 104
  • Ground fault in the compressor or its wiring — detail code 104
  • Current sensing circuit fault — detail code 103, sometimes the least expensive outcome
  • Supply voltage problems stressing the inverter, often alongside bus voltage codes
  • Mechanical compressor problems causing it to draw excessive current under load

What happens if you leave it

Unlike most codes, the risk here is not gradual degradation. It is acute.

Repeatedly restarting against a genuine overcurrent condition can cascade. The most costly outcome we see is a building that reset 4250 many times over a weekend to keep tenants comfortable, and converted a compressor failure into a compressor and inverter failure.

If you are seeing 4250, the correct action is to leave the system off and get it diagnosed.

What we check

  1. Record the detail code — this drives everything that follows.
  2. Electrical testing on the compressor — winding resistance and insulation, to establish whether the compressor is the fault.
  3. Test for ground faults in the compressor and its wiring.
  4. Inspect the inverter board and power module for visible failure and test operation.
  5. Verify current sensing circuits — occasionally the fault is in measurement rather than current.
  6. Check supply voltage quality, since supply problems present as inverter faults.
  7. Assess refrigerant contamination if the compressor has failed electrically, because that changes the scope of the repair.

What you can tell us before we arrive

  • The detail code in brackets. If nothing else, this one. Photograph the controller before resetting.
  • How many times has it been restarted? This genuinely changes what we expect to find.
  • Was there a supply issue? Outage, surge, or known voltage problems in the building.
  • Any noise from the outdoor unit before it stopped? Mechanical compressor problems often announce themselves.
  • 4220 — Bus voltage abnormality. Supply-side problems that can present alongside inverter faults.
  • 4240 — Overload protection. Sustained high load rather than acute overcurrent.

Do not restart it. Get it diagnosed.

We are certified on Mitsubishi, Daikin and LG VRF platforms, and we service systems we did not install.

Next business day service for commercial VRF.

Frequently asked questions

What does error code 4250 mean on a Mitsubishi City Multi system?

It is an overcurrent fault on the inverter. Current drawn by the compressor circuit exceeded safe limits and the system shut down. It covers several distinct conditions, and the detail code shown alongside it identifies which one you actually have.

Why does 4250 come with a number in brackets?

That is the detail code, and it is the most useful information on your controller. It distinguishes an inverter power module fault from a short-circuited compressor motor. Those are very different repairs at very different costs, so record it before resetting anything.

Is error 4250 a failed compressor?

Sometimes. Detail code 105 indicates overcurrent from a short-circuited motor, which points at the compressor itself. Other detail codes point at the inverter board or its sensing circuits. Diagnosis must establish which, because guessing wrong is expensive in both directions.

How much does a 4250 error cost to repair?

This is potentially the most expensive fault on a VRF system. Board-level faults are moderate by comparison. A short-circuited compressor is the highest-cost repair there is, involving the component itself plus refrigerant recovery, system cleanup where contamination occurred, and significant labour in a commercial setting.

Can I keep resetting a 4250 error?

No, and this is the code where that matters most. If the underlying condition is a genuine short or ground fault, repeated restarts drive fault current through components that are already compromised, and can take a healthy inverter down along with a failed compressor.

What is the difference between 4250 and 4240?

Both are current-related, but 4240 is overload protection responding to sustained high load over time, while 4250 is overcurrent covering acute faults including short circuits and power module failures. 4250 generally indicates something electrically broken rather than a system simply working too hard.

Certified on all three VRF platforms

Daikin, Mitsubishi and LG. We service commercial VRF systems we did not install — including buildings whose original contractor is no longer available.

Next business day commercial service.

Equipment scope: City Multi PURY and PUHY series (P72–P288). Cost bands reflect our typical commercial service experience and vary with system size, access and site conditions. This page is a guide for building owners and facility managers, not a repair procedure.